Diesel Generators for Indonesian Mines: Prime Power Sizing

A mine is a prime-power site, not a standby site: the sets run for most of the year, and the plant is sized from the running load plus the largest motor started across the line, not from a round kVA number. A 1,100 kW Indonesian mine load with a 250 kW ball mill on a direct-on-line start points to 3 × 1,000 kVA prime sets in N+1 – two running near 70% load, one standby – burning about 264 L/h and 6,400 L/day at 50 Hz, 380 V. The steps below show how that answer is reached and where it changes.

Prime power, not standby

A mining plant is the clearest case of prime duty on this site: where there is no grid, the sets are the grid. The load runs 24 hours a day for weeks at a time, and the engines spend most of their life between 60% and 90% of rated output. That is a different machine from a standby set that starts twice a year and runs for a day.

The difference is set out in prime vs standby power: a prime set is rated for continuous variable load with a load factor allowance, while a standby set is rated for the duration of an outage. Specifying a standby-rated set and running it as prime shortens the overhaul interval and burns more fuel per kilowatt-hour than the rating promises. For a mine, write “prime” or “continuous” into the specification first, then choose the kVA.

Why 50 Hz changes the Indonesian build

Indonesia runs 220 V single-phase and 380 V three-phase at 50 Hz, so the same frame turns at 1,500 rpm instead of the Philippine 1,800 rpm at 60 Hz. The alternator is wound for 50 Hz, the engine is governed for 1,500 rpm, and the derating and current figures are read from a 50 Hz datasheet, not a 60 Hz one. The full split is in 50 Hz vs 60 Hz generators.

The practical consequences for a mine are three. First, 50 Hz sets are quoted at 380/220 V, 0.8 power factor, the same convention used in the rest of this site. Second, a 50 Hz motor has a lower synchronous speed, which is easier on the drivetrain but does not remove the starting current – the starting kVA still decides the bus. Third, the enclosure envelope is the same as the 60 Hz version, so transport and footprint do not change.

Step 1: build the load list, then find the largest motor

The plant is sized from the load list with diversity applied, not from a count of motors. A mine list is a few large drives and a long tail of small loads, and the largest motor – not the total – is what forces the set count up. The table below is a representative 1,100 kW plant; treat it as a model, not as a survey of any particular site.

Representative mine load list, 1,100 kW running after diversity. Start step is the transient kVA the bus must absorb; the ball mill is the number that drives the plant design.
Load Running kW Start method Start step
Ball mill 250 Direct-on-line about 1,875 kVA (6 × running)
Crusher 160 Soft starter about 450 kVA (2.5 ×)
Conveyors, six drives 120 Direct-on-line, largest single about 180 kVA
Dewatering pumps, three 150 Direct-on-line, largest single about 280 kVA
Slurry pump 110 Variable speed drive about 150 kVA
Ventilation fans 90 Direct-on-line about 170 kVA
Camp, offices, lighting 120 Stepped, across the line small, staggered
Workshop and small loads 100 Direct-on-line small, staggered
Total, diversity applied 1,100 largest step about 1,875 kVA

The ball mill row is the one that decides the plant. At six times running current its starting step is about 1,875 kVA – bigger in kVA terms than the whole running plant for a few seconds. That is why the answer is a paralleling bus with more than one set, rather than one large set sized to the peak: the bus must carry the running load plus the start step without the voltage dipping far enough to drop contactors. The load-list method is worked through in how to size a diesel generator.

Step 2: prime, continuous or N+1

Three duty names appear on mine specifications, and they are not interchangeable.

Duty ratings for a mine plant. Hours are the ruling number: a set bought for the wrong duty is either under-used or being worn out on a schedule nobody planned.
Duty Load factor Hours per year Where it fits on a mine
Standby 70% of standby rating, intermittent a few hundred Camp emergency, ventilation, communications
Prime 70% average of prime rating, variable load unlimited Most mine power plants
Continuous 100% of rating, constant load unlimited Base-load crushers and mills running flat out

For 1,100 kW of running load plus a 1,875 kVA start step, two 1,000 kVA prime sets running give 1,600 kW of capacity between them – about 69% load, inside the efficient band – and the bus shares the ball mill transient. The third set is the N+1: it is not a spare sitting in a crate, it is a running asset that lets one engine be serviced while the plant keeps producing. The argument for N+1 over one big set is set out in generator paralleling and N+1.

Step 3: derating for heat, humidity and altitude

Indonesian sites are hot and humid rather than high: most mine and smelter sites sit near sea level with 30-35 °C ambient and high relative humidity, while a few highland sites add altitude. The derating is applied to the engine and alternator before the set is chosen, and it is read from the datasheet, not guessed.

Planning derating allowances for Indonesian sites. These are stated assumptions to start a quotation, not datasheet values; the engine and alternator curves govern.
Condition Planning allowance Notes
Ambient 40 °C no derate ISO 8528-1 reference temperature
Ambient 45 °C about 5% off output verify against the engine datasheet
Altitude above 1,000 m about 3% per 300 m highland sites only; most Indonesian mines are coastal or lowland
High humidity, coastal salt no direct output derate changes the enclosure and corrosion specification, not the rating

The derating is applied before the load is matched, which means a site that needs 1,000 kW at 45 °C is not quoted from the 40 °C datasheet. In practice the 5% allowance at 45 °C moves a 1,000 kVA prime frame down by about 40 kW, and that is enough to change the set count if the margin was already thin.

Step 4: fuel at a remote site

Fuel is the largest operating cost of a mine power plant, and on a remote Indonesian site the constraint is logistics, not price. The burn figures below are the same planning values used across this site: 0.24 L/kWh at 75% load, 0.25 at 50%, 0.30 at 25% and 0.235 at 100%, at 0.8 power factor.

Fuel burn by frame at 50 Hz, 0.8 PF. Litres per hour, with specific consumption in L/kWh in brackets. Use the 75% column for budgeting; the 25% column shows the cost of running lightly loaded.
Frame kW prime 25% load 50% load 75% load 100% load
800 kVA 640 48 L/h (0.30) 80 L/h (0.25) 115 L/h (0.24) 150 L/h (0.235)
1,000 kVA 800 60 L/h (0.30) 100 L/h (0.25) 144 L/h (0.24) 188 L/h (0.235)
2,000 kVA 1,600 120 L/h (0.30) 200 L/h (0.25) 288 L/h (0.24) 376 L/h (0.235)

Indonesian diesel is supplied as a biodiesel blend – B30 to B35 depending on the year and the supply contract – and that changes how the fuel is stored. FAME holds water and grows microbes faster than straight diesel, so a remote bulk tank needs a polishing loop, regular water draw-off and a six-month test regime rather than a fill-and-forget schedule. The storage and day-tank logic is set out in fuel consumption and day tanks; the Philippine B2 case there is the same method applied to a different blend.

Fuel system for the worked 1,100 kW plant at 75% load. Sizes are planning figures for a single site; a multi-plant site multiplies the bulk storage by the number of independent plants.
Item Planning figure Why it is that number
Plant burn 264 L/h, about 6,400 L/day 1,100 kW at 0.24 L/kWh
Day tank per set 1,000 L about 7 hours at one set’s 75% burn of 144 L/h
Bulk tank 45,000 L seven days of autonomy, with 110% bunding
Polishing recirculation loop, 24 h removes water and sediment before the day tanks
Testing monthly draw-off, 6-month lab sample catches water, microbes and blend degradation

Step 5: containerised or skid, and how it gets to site

Indonesian mine sites are reached by barge and unsealed road, so the set usually travels as a containerised or skid package rather than a bare frame. The choice is between a 20 ft container that becomes the engine room on arrival, and a skid that has to wait for a building.

Form factor for a remote Indonesian mine site. The container is the default for large prime sets; the canopy is for camp and support loads.
Form Fits Limits
20 ft containerised Walk-in service in the wet season, standard lifting, secure transit Heavier and wider on the final road leg
Skid under a roof Lower first cost where a building already exists Needs the building before the set is useful
Canopy Camp supply, workshops, small dewatering pumps Limited for large prime sets and dusty yards

The containerised path is also how Indonesian data centres are supplied, and the transport, tank and test scope carries over directly – see containerised generators for Indonesia data centres and the containerised sets page.

Step 6: dust, salt and the wet season

Dust is the mine’s own weather. Airborne fines load the air filter and the radiator, and when they get wet they conduct, so the electrical joints in the control panel fail first. The answer is heavy-duty air filtration, a sealed enclosure and a shorter service interval; a filter that lasts 500 hours on a clean site lasts a fraction of that beside a crusher.

Coastal and smelter sites add salt and humidity, which corrode terminals, hinges and the enclosure itself before the engine notices. Specify a corrosion-rated enclosure, sealed connectors and a wet-season service plan. These are the same site-condition rules applied on the diesel generators for mining page.

Step 7: control, synchronising and load management

Two or more sets on one bus need a paralleling controller with load sharing, load-dependent start and stop, and synchronising. Load-dependent start and stop is what keeps the running sets near their efficient band while the plant load swings: instead of running all three sets lightly, the controller starts and stops sets so the ones running sit near 70-85% load.

This is not a luxury. A set run below about 40% load for long periods wets its exhaust and glazes its bores, and its fuel per kilowatt-hour climbs sharply – the 0.30 L/kWh at 25% load in the fuel table is the same engine costing 25% more per delivered kilowatt. The control and protection scope is in generator paralleling and N+1.

A worked Indonesian mine plant

The table below closes the loop on the numbers used above. It is a planning model, not a quotation.

Worked plant for a 1,100 kW Indonesian mine at sea level, 40 °C reference.
Item Value
Running load 1,100 kW, diversity applied
Largest start step about 1,875 kVA (250 kW ball mill, direct-on-line)
Sets 3 × 1,000 kVA prime, 800 kW at 0.8 PF
Duty N+1 – two running at about 69% load, one standby for service
Electrical 380/220 V, 50 Hz, 1,500 rpm, three phase
Build 20 ft containerised, dust filtration, heavy-duty air cleaner
Control Paralleling with load sharing and load-dependent start and stop
Fuel 1,000 L day tank per set, 45,000 L bulk tank, polishing loop; 264 L/h and 6,400 L/day at 75% plant load
Derating 40 °C reference; apply about 5% at 45 °C; no altitude derate at sea level

The 1,000 kVA frame is the building block here because it is large enough to carry half the plant alone and small enough to be barged and trucked without special permits on most Indonesian routes. The same frame is listed on the 1000 kVA diesel generator page.

What this model does not cover

  • Every figure is a planning value at 50 Hz, 380/220 V, 0.8 power factor and a 40 °C reference; the engine and alternator datasheets govern, and the factory test report wins where they differ.
  • Fuel burn uses 0.24 L/kWh at 75% load, 0.25 at 50%, 0.30 at 25% and 0.235 at 100% – stated planning assumptions, not guaranteed consumption.
  • The Indonesian biodiesel blend is described in general terms; the delivered product certificate and the site fuel specification govern.
  • No mine name, location, certification or delivery claim is made. The site is described by its load and its conditions only.
  • Nothing here is a quotation. Freight, barge legs, duties, civils and commissioning are separate scopes and are priced separately.

Frequently asked questions

How do you size a generator plant for a mine?

From the running load with diversity applied, plus the largest motor started across the line. A 1,100 kW plant with a 250 kW ball mill on direct-on-line start has a start step of about 1,875 kVA, which is what forces the plant to a paralleling bus and N+1 rather than a single large set. The method is the same one in how to size a diesel generator.

Prime or standby for a mine that runs 24 hours a day?

Prime, or continuous if the load is constant. A prime set is rated for unlimited hours at about 70% average load, while a standby set is rated for the duration of an outage – running a standby set as prime shortens its overhaul interval. Write the duty into the specification before choosing the kVA.

How much fuel does a mine power plant burn?

About 264 L/h and 6,400 L/day for a 1,100 kW plant at 75% load, using the site’s planning figure of 0.24 L/kWh. At 25% load the same energy costs 0.30 L/kWh, so a lightly loaded plant burns more fuel per delivered kilowatt, not less. The frame-by-frame table is in the fuel section above.

What derating applies in Indonesia?

Most Indonesian mines are coastal or lowland, so the main allowance is heat: about 5% off output at 45 °C against the 40 °C reference, with a further allowance of about 3% per 300 m only for highland sites above 1,000 m. High humidity and salt change the enclosure and corrosion specification rather than the rating.

Containerised or skid for a remote site?

Containerised is the default for large prime sets: the container becomes the engine room on arrival, is handled with standard lifting gear, and gives the service team a weatherproof place to work in the wet season. A skid only wins where a building already exists, and a canopy suits camp and support loads.

Can one big set replace three smaller ones?

Not cleanly. One big set still has to absorb the ball mill start step and then runs lightly loaded between starts, which wets the exhaust and raises fuel burn per kilowatt-hour. N+1 also means one set can be serviced without stopping production. The trade-off is worked through in generator paralleling and N+1.

Send the load list, the largest motor and the site

Running load in kW, the largest motor and how it starts, site altitude and ambient, the days of fuel autonomy required, and the delivery point. The reply sets out the set count and rating, the duty, the derating applied, the daily fuel burn and the tank sizes – with every assumption stated, so the numbers can be checked against the datasheet.

Request a quote WhatsApp the sales desk

Written and maintained by the kvagenset sales engineering desk. Ratings are 50 Hz, 380/220 V, 1,500 rpm and 0.8 power factor for Indonesian projects; fuel burn of 0.24 L/kWh at 75% load, 0.25 at 50%, 0.30 at 25% and 0.235 at 100%, a 40 °C ambient reference with about 5% derating at 45 °C, and about 3% derating per 300 m above 1,000 m altitude are stated planning assumptions, not datasheet values or guarantees. The Indonesian biodiesel blend is described in general terms only and the delivered product certificate governs. Reviewed 4 November 2026. The mining application is summarised on the diesel generators for mining page, and the Indonesian delivery context is set out under diesel generators for Indonesia.